D.4  

HiPath 3500 Board Power Requirement 
 

 Table D-7   Nominal Output of the HiPath 3500 Power Supply Units
 Power Supply Unit  
 Part Number  
 Max. Nominal Output in W  
 5 V  
 -48 V  
UPSC-DR  
S30122-K7373-A900  
S30122-K7373-M900  
 40.0  
 53.0  
Powerbox PB3000 with LUNA2  
S30177-U773-X with S30122-K7686-M1  
 -  
 110  
You must check whether the total power requirement of the boards used and the workpoint clients connected exceeds the maximum possible output of the UPSC-DR with or without Powerbox PB3000. Section D.7 "Checking Whether the Output of a Power Supply Unit is Sufficient" contains a sample calculation.  

 Table D-8   HiPath 3500 Board Power Requirement
 Board or Component  
 Part Number  
 Net Power Requirement in W  
 5 V  
 -48 V  
BS3/1  
S30807-H5482-X  
 -  
 2.0  
BS3/3  
S30807-H5485-X  
 -  
 3.0  
CBRC (including subboards)  
S30810-Q2935-Z301  
 7.0  
 0.5  
HXGR3  
S30810-K2943-Z  
 10.0  
 -  
IVMS8R  
S30122-K7379-Z  
 2.6  
 0.3  
Fan for HiPath 3500  
-  
 -  
 1.4  
P DM1  
S30807-Q5692-X100  
 -  
 5.0  
SLAD8R  
S30810-K2956-X300  
 2.0  
 1.0  
SLU8R  
S30817-K922-Z301  
 0.8  
 -  
STLS4R  
S30817-K924-Z313  
 1.0  
 -  
STRBR  
S30817-Q932-Z  
 0.5  
 -  
T CASR-2  
S30810-K2945-X  
 4.5  
 -  
TLA4R  
S30817-Q923-Zxxx  
 0.2  
 -  
TMGL4R  
S30810-K2918-Z  
 5.71  
 0.11  
TST1  
S30810-K2919-Z  
 0.8  
 -  
TS2R  
S30810-K2913-Z300  
 0.9  
 -  
8SLAR  
S30810-K2925-Z  
 1.3  
 1.3  
1Identified at a traffic flow of 0.8 Erlang